Water cooling thermal power measurement in a vacuum diffusion pump

Water cooling thermal power measurement in a vacuum diffusion pump

Authors

  • Luís Henrique Cardozo Amorin Universidade Estadual de Londrina
  • Paulo Rogério Catarini da Silva Universidade Estadual de Londrina
  • Jair Scarminio Universidade Estadual de Londrina
  • Alexandre Urbano Universidade Estadual de Londrina

DOI:

https://doi.org/10.5433/1679-0375.2012v33n1p67

Keywords:

Diffusion Pump, Closed circuit refrigeration, Vacuum system

Abstract

Diffusion vacuum pumps are used both in industry and in laboratory science for high vacuum production. For its operation they must be refrigerated, and it is done by circulating water in open circuit. Considering that, vacuum systems stays operating by hours, the water consumption may be avoided if the diffusion vacuum pumps refrigeration were done in closed circuit. However, it is necessary to know the diffusion vacuum pump thermal power (the heat transferred to circulate water by time units) to implement one of these and get in the refrigeration system dimension. In this paper the diffusion vacuum pump thermal power was obtained by measuring water flow and temperature variation and was calculated through the heat quantity variation equation time function. The thermal power value was 935,6 W, that is 397 W smaller and 35 W bigger than, respectively, the maximum and minimum diffusion pump thermal power suggested by its operation manual. This procedure have been shown useful to precisely determine the diffusion pump thermal power or of any other system that needs to be refrigerated in water closed circuit.

Downloads

Download data is not yet available.

Author Biographies

Luís Henrique Cardozo Amorin, Universidade Estadual de Londrina

Aluno de Mestrado em física da Matéria Condensada, Departamento de Física - UEL

Paulo Rogério Catarini da Silva, Universidade Estadual de Londrina

Docente do Departamento de Física, Universidade Estadual de Londrina

Jair Scarminio, Universidade Estadual de Londrina

Docente do Departamento de Física, Universidade Estadual de Londrina

Alexandre Urbano, Universidade Estadual de Londrina

Docente do Departamento de Física da Universidade Estadual de Londrina, bolsista de produtividade D&T

Published

2012-04-25

How to Cite

Cardozo Amorin, L. H., Catarini da Silva, P. R., Scarminio, J., & Urbano, A. (2012). Water cooling thermal power measurement in a vacuum diffusion pump. Semina: Ciências Exatas E Tecnológicas, 33(1), 67–72. https://doi.org/10.5433/1679-0375.2012v33n1p67

Issue

Section

Original Article

Most read articles by the same author(s)

Loading...